Guide · Homeowners · 3 min read · Updated 17 November 2026
30 vs 60 Minute Fire Rated Walls: Which Do You Need?
Short answer
A 30 minute fire rated wall resists fire for at least 30 minutes, and is typical for protected stairways in houses, garage separation and many internal escape routes. A 60 minute wall resists for at least 60 minutes and is common for compartment walls in flats, HMOs, commercial premises and protected shafts. The rating you need is set by Approved Document B, building control or a fire risk assessment.
What the fire rating means
A fire rating describes how long a wall system has been shown to resist fire in a standard furnace test. The wall must keep its structural strength if it is load-bearing, stop flames and hot gases passing through, and limit the temperature rise on the side away from the fire. These are known as loadbearing capacity, integrity and insulation, often written as R, E and I.
Walls are tested to standards such as BS 476 Part 22 or BS EN 1364-1, and classified under BS EN 13501-2. A classification such as EI 60 means the wall maintained integrity and insulation for 60 minutes. Crucially, the rating only applies to the system as tested. Change the board, studs, fixings or insulation and the rating no longer applies.
Where each rating is typically required
The required rating depends on the building, its use, its height and the role of the wall. The examples below are typical, but the actual requirement for your project should come from building control, your designer or a fire risk assessment.
| Situation | Typical requirement | Why |
|---|---|---|
| Protected stairway in a house with a loft conversion | 30 minutes | Protect the escape route from upper floors |
| Wall between integral garage and house | 30 minutes | Separate a higher-risk area from living space |
| Walls to escape corridors in many flats | 30 minutes or more | Protect the route out |
| Compartment walls between flats | 60 minutes or more | Contain fire within one dwelling |
| Walls around plant rooms and service risers | Often 60 minutes or more | Higher fire load and vertical spread |
| Commercial compartment walls | 60 minutes or more | Set by building use and size |
How 30 and 60 minute walls are built
A typical 30 minute partition uses a single layer of 12.5 millimetre fire-resistant plasterboard on each side of a metal or timber stud frame, though the exact specification varies by manufacturer. A typical 60 minute partition uses two layers of fire-resistant board each side, or a single layer of a thicker specialist board, often with mineral wool in the cavity.
In both cases, the details make the difference. Board joints must be staggered between layers, screws must be at the specified centres, and the head and edges of the wall must be sealed. The wall must run up to the structural soffit, the underside of the floor or roof above, not stop at a suspended ceiling, unless the system has been tested with a fire-rated ceiling.
- Follow the manufacturer's tested system exactly
- Run the wall to the structural soffit, not just a false ceiling
- Stagger joints between board layers
- Use the specified screws and fixing centres
- Seal every pipe, cable and duct penetration with tested products
- Fit fire doors with matching performance and correct frames
Doors, glazing and openings
A fire rated wall with an ordinary door in it does not provide fire resistance. Doors in a 30 minute wall usually need an FD30 fire door set, and in a 60 minute wall an FD60, with frames, hinges, intumescent strips and smoke seals where required, and self-closing devices where the regulations call for them. The door must be installed as a complete tested set.
Glazing in a fire rated wall must also be fire-resistant glass in a tested frame. Ventilation grilles and other openings need suitable fire dampers or intumescent grilles. These details often cost more than the wall itself, so include them in your budget from the start.
Combining fire and sound performance
Many walls need both fire resistance and sound insulation, for example between flats or hotel rooms. Manufacturers publish systems tested for both, which typically use acoustic and fire-resistant board, mineral wool insulation and sometimes resilient bars. Using a combined system from the outset is cheaper than trying to add acoustic performance to a fire wall later, and avoids accidentally invalidating the fire rating by mixing products.
Choosing the right rating
If you are carrying out building work, building control will confirm the requirements under Approved Document B in England. For existing commercial premises, HMOs and the common parts of blocks of flats, the Regulatory Reform (Fire Safety) Order 2005 requires the responsible person to carry out a fire risk assessment, which may recommend upgrades to a specific rating. Insurers sometimes set their own requirements.
Building to a higher rating than required is possible, and some owners choose 60 minutes for extra margin. It costs more, typically £75–£120 per m² compared with £55–£85 per m² for 30 minutes, and adds thickness, so it should be a deliberate choice rather than a default.
Upgrading an existing wall
Existing walls can often be upgraded rather than rebuilt. A sound plastered masonry wall may already provide good fire resistance, while an old stud partition with lath and plaster or a single layer of standard plasterboard may not. Upgrading to 30 minutes typically means fixing an additional layer of fire-resistant board to one or both sides to a published upgrade specification, at £35–£65 per m².
Reaching 60 minutes on an existing stud wall usually needs more layers or replacement of the boards altogether, which can be close to the cost of a new wall. A specialist will check what the existing wall is made of before recommending the most economical route. A specialist can show you the published data for each option so you can see what you are paying for.
Questions people also ask
What does EI 30 or EI 60 mean on a wall?
EI is a fire resistance classification under BS EN 13501-2. E stands for integrity, meaning flames and hot gases are kept out, and I stands for insulation, meaning the unexposed side stays below set temperature limits. The number is the time in minutes the tested system achieved both.
Is a 60 minute fire wall twice as thick as a 30 minute one?
Not necessarily, but it is usually thicker. A typical 30 minute partition has one layer of fire-resistant board each side, while 60 minutes usually needs two layers each side or a thicker specialist board, often with insulation in the cavity. The exact build depends on the manufacturer's tested system.
Can I use normal plasterboard for a fire rated wall?
Standard plasterboard has some fire resistance, but fire rated walls are built to tested systems that usually specify fire-resistant board, often coloured pink or red, with set studs, fixings and insulation. Mixing products or substituting standard board means the wall cannot be relied on to achieve the rating.
Written and checked by the Fire Rated Walls team. Read our editorial policy.
More guides
How Much Does a Fire Rated Wall Cost in the UK?
A new fire rated stud partition in the UK typically costs £55–£85 per m² for 30 minutes and £75–£120 per m² for 60 minutes. Upgrading an existing…
Loft Conversion Fire Protection: What the Rules Require
When a loft conversion adds a new storey to a typical house in England, Approved Document B normally requires a protected escape route from the new…
Integral Garage Fire Separation: Walls, Doors and Ceilings
The walls and ceiling between an integral or attached garage and the house should provide fire resistance, typically 30 minutes, with any door…
What Is Fire Stopping? Penetrations, Products and Rules
Fire stopping is the sealing of gaps and openings in fire resisting walls and floors, such as holes around pipes, cables and ducts, so fire and smoke…